Motor starters
In general miniature circuit breakers can give only short
circuit protection to motor loads due to high starting
currents which may be encountered: typically 3 to 12 times
full load current (FLC)
Assumptions
The tables give recommended mcb ratings for motors up
to 37kW based on the following assumptions:
Direct on-line starting
starting current = 7 x FLC
run up time =
6 seconds, motors < 3 kW
10 seconds, motors < 22 kW
running currents = average values only
(individual manufacturers figures may vary)
four pole motors i.e. speed approx.
1500 rev/min.
For Higher inertia loads i.e. hoists and fans run up
times maybe considerably longer than those assumed above.
The rating of the mcb must take account of the greater
run-up time and starting current. The required mcb rating
can be determined by reference to time/current curves
(consult us)
Star/ delta starting
Since, during the changeover from star to delta, a high
current surge in the order of DOL values may be met,
the mcb rating selected should be the same as that
recommended for DOL starting